High Frequency On Line UPS HP H 3K
APPLICATION
Servers, Data-centers, Critical network devices, Sensitive electronic equipment, Telecom...
KEY FEATURES
l DSP Control
l Fully digital control technology provides a highly accurate,drift-proof control
compared to traditional analog electronics
l Optional language by LCD dispaly(English,russian,German,French,Spanish)
l Input power factor is more than 0.98,Output power factor is 0.9
l Optional output frequency,50 or 60HZ automatic or configurable as a frequency converter
l Batttery intelligent management
l Smart RS-232,intelligent slot,USB and EPO communication port
TECHNICAL SPECIFICATIONS
MODEL
|
|
H 1K
|
HP 1.5K
|
H 2K
|
H 3K
|
CAPACITY
|
VA/W
|
1000VA/700W
|
1500VA/1050W
|
2000VA/1400W
|
3000VA/2100W
|
INPUT
|
Nominal Voltage
|
100/110/120/127 VAC or 220/230/240 VAC
|
Operating Voltage Range
|
60-138VAC or 120-276VAC
|
Frequency Range
|
40 to 70 Hz before transfer to battery , automatic selection of nominal frequency 50/60Hz for Inverter to match Input (Auto Sync.)
|
Phase
|
Single Phase
|
Power Factor
|
> 0.98
|
Cold Start(0 to 100% load)
|
Yes
|
OUTPUT
|
Voltage
|
100, 110, 120, 127 VAC(±2%) or 200, 208, 220, 230, 240 VA(±2%)
|
Frequency
|
50 or 60 Hz Automatic or configurable as a frequency converter
|
Wave form
|
Sine Wave
|
Power Factor
|
0.7
|
Voltage Distortion
|
R Load: < 3 % THD;RCD Load: < 5 % THD
|
Overload Capacity
|
Transfer to bypass if available or else shut down after the following:100% < load < 102%,overload warning;102% < load < 130%, 12s;130% < load < 150%, 2s
|
Current Crest Ratio
|
3:1
|
Connection
|
Hardwired
|
EFFICIENCY
|
|
>82% (1 kVA) >84% (2-3kVA)
|
BATTERY
|
Type
|
Valve Regulated Lead Acid (VRLA), minimum 3 years float service life at 25℃
|
Nominal DC Voltage
|
36VDC
|
96VDC
|
Quantity
|
3x6V9Ah
|
4x12V/7Ah
|
4x12V/9Ah
|
8x12V/7Ah
|
TRANSFER TIME
|
0ms(no break) in Online mode, 5 ms max in High Efficiency mode due to loss of utility
|
Bypass
|
|
Automatic bypass to provide an alternate path to utility power in the case of overload, or internal failure
|
|
Bypass is permitted only when Frequency is within ±5 HZ of nominal and Voltage is within +10 / -15 V (CS) of nominal outside this range bypass is NOT AVAVAILABLE and WILL NOT occur (CS)
|
User interface
|
LCD display
|
UPS status, I/P& O/P voltage & frequency,Battery voltage,Battery capacity,Loading, Temprature, History record
|
Language
|
English, German, French, Spanish, Russian (other language packs can be loaded)
|
Communications
|
DB-9 port
|
RS-232, XCP, Relay mode
|
Intelligent Slot
|
Options: SMNP Card, AS400 Card or Winpower CMC / USB Por
|
Enviromental
|
Operating temperature
|
(at sea level) 0-40℃ Online Mode. The unit will be derated linearly for altitude, Max altitude refer to 10.5.
|
NOTE: Thermal protection in case of overheating switches Load to Bypass.
|
Operating humidity
|
5 - 90% Non-condensing
|
Acoustic Noise
|
<45dB <45dB <50dB (2000~3000VA)
|
Physical Fea
|
Weight
|
10
|
15
|
20
|
24.5
|
Dimensions(W x H x D)mm
|
355x145x22O
|
355x145x22O
|
338x190x318
|
433x190x318
|
|
|